2-6. Ventilated area
•
Ensure that the area is in the open or that it
is adequately ventilated before breaking into
the system or conducting any hot work.
•
A degree of ventilation shall continue during
the period that the work is carried out.
•
The ventilation should safely disperse any
released refrigerant and preferably expel it
externally into the atmosphere.
2-7. Checks to the refrigerating equipment
•
Where electrical components are being
changed, they shall be fi t for the purpose
and to the correct specifi cation.
•
At all times the manufacturer’s maintenance
and service guidelines shall be followed.
•
If in doubt consult the manufacturer’s
technical department for assistance.
•
The following checks shall be applied to
installations using fl ammable refrigerants.
-
The refrigerant charge is in accordance
with the room size within which the
refrigerant containing parts are installed.
-
The ventilation machinery and outlets
are operating adequately and are not
obstructed.
-
If an indirect refrigerating circuit is being
used, the secondary circuit shall be
checked for the presence of refrigerant.
-
Marking to the equipment continues to be
visible and legible. Markings and signs
that are illegible shall be corrected.
-
Refrigerating pipe or components are
installed in a position where they are
unlikely to be exposed to any substance
which can corrode refrigerant containing
components, unless the components
are constructed of materials which are
inherently resistant to being corroded or
are properly protected against being so
corroded.
2-8. Checks to electrical devices
•
Repair and maintenance to electrical
components shall include initial safety
checks and component inspection
procedures.
•
Initial safety checks shall include but not
limit to:-
-
That capacitors are discharged: this
shall be done in a safe manner to avoid
possibility of sparking.
-
That no live electrical components and
wiring are exposed while charging,
recovering or purging the system.
-
That there is continuity of earth bonding.
•
At all times the manufacturer’s maintenance
and service guidelines shall be followed.
•
If in doubt consult the manufacturer’s
technical department for assistance.
•
If a fault exists that could compromise safety,
then no electrical supply shall be connected
to the circuit until it is satisfactorily dealt with.
•
If the fault cannot be corrected immediately
but it is necessary to continue operation, an
adequate temporary solution shall be used.
•
The owner of the equipment must be
informed or reported so all parties are
advised thereinafter.