Olimpia Splendid Sitali CX 120 handleiding
Handleiding
Je bekijkt pagina 29 van 32

29
Information on disposal of units at the end of life.
ThisproductcomplieswithEUDirective2002/96/EC.
Thesymbolofthecrossed-outdustbinindicatesthatthisproductmustbecollectedseparatelyfromotherwaste
at the end of its life. The user must, therefore, dispose of the product in question at suitable electronic and
electro-technical waste disposal collection centres, or else send the product back to the retailer when purchasing
anew,equivalenttypedevice.
Separate collection of decommissioned equipment for recycling, treatment and environmentally compatible
disposalhelpstopreventnegativeeffectsontheenvironmentandonhealthandpromotestherecyclingofthe
materials that make up the equipment.
Improperdisposaloftheproductbytheusermayresultinadministrativesanctionsasprovidedbylaw.
9 DISPOSAL AND RECYCLING
Fig. 8.k
• Cleanthefanseveryyearwithavacuumcleaner.Thismaydifferpersituationdependingoninternalandexternalenvironmental
conditionsandonfrequencyoffiltercleaning.Donotmovethebalanceclipsofthefan(Fig.8.e-h-k).
8.5 Troubleshooting
Fans do not start
1.Checkthatmainsupplygetstotheunit.
2. Check that all connections are working (all connections in terminal box and fast couplings of intake and exhaust air fans).
Led on CTRL-V lights on
1.Check paragraph 7
Reducedairow
1. Check setting of fan speed in the terminal box or remote controller.
2. Check filters. Change of filters required?
3. Check diffusers. Re-setting or cleaning of grilles and diffusers required?
4. Check fans and heat exchange block. Cleaning required?
5. Check if air intake and exhaust have been clogged.
6.Checkductingsystemfordamageand/ordirtaccumulation.
Fan noise/vibrations
1. Clean fan impellers. Cleaning required?
2.Checkthatthefansarermlyinplacewithintheunit.
Excessive air noise
1. Check setting of fan speed in the terminal box or remote controller.
2. Check grilles and diffusers. Re-setting or cleaning of grilles and diffusers required?
Gurgling noise
1.Drainconnectionshavenotbeeninstalledcorrectly.
2. Drain connection has a too low water level, fill it up with water.
Unpleasantsmell
1.Drainconnectionshavenotbeeninstalledcorrectly.
2. Drain connection has a too low water level, fill it up with water.
3. Check filters. Change of filters required?
4.Checkductingsystemandgrillesanddiffusers.Cleaningrequired?
Water leakage near the unit
1.Drainconnectionshavenotbeeninstalledcorrectly.Checkingnecessary?
2.Drainconnectionsaredirty.Cleaningnecessary?