ID Name Description Permitted values
CF Conguration Congure the type of control
AU : Autonomous
rE : Remote
bU Bus Protocol Allows to congure the type of bus used
AS : ASCII
rt : RTU
Ad Unit Address
Allows to set/change the unit address
(insert the value in hexadecimal format)
00 -> FF (255)
Fa Fancoil Type
Allows to select the type of
fancoil
_0: Without ap (200-1000)
_1: All versions
(1100-1400-1600)
_2: With ap (200-1000)
Po Position of installation
Allows to select where the fancoil has
been installed
uP : roof installation
dO : oor installation
co
Ambient temperature
compensation
Allows to choose the compensation
value to use
-5 : 5
bU – BUS Protocol:
Modicon Modbus” ASCII type Modicon Modbus RTU type
Baudrate = 9600
Baudrate = 9600
data bits = 7 data bits = 8
stop bit = 1 stop bit = 1
equality = yes equality = no
Ad - Unit Address:
In the event of need, it is possible to change the unit address.
The value must be entered in hexadecimal format.
The table below indicates the conversion of the rst 80 numbers from decimal to hexadecimal format, for
the next numbers, please refer to the specic tables which can be consulted on the web.
Decimal Hexadecimal
1 01
2 02
3 03
4 04
5 05
6 06
7 07
8
08
9 09
10 0A
11 0B
12 0C
Decimal Hexadecimal
13 0D
14 0E
15 0F
16 10
17 11
18 12
19 13
20 14
21 15
22 16
23 17
24 18