Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl
Space For Intake Air in Feet
Standard Termination at Elevation 0 - 2,000 ft
Number
of 90°
Elbows
Used
1-1/2” Pipe 2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity Capacity
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 15 10
n/a n/a n/a
71 56 34 14
n/a
100 100 78 43
n/a
118 117 98 98 60
2 10
n/a
66 51 29 9 95 95 73 38 113 112 93 93 55
3
n/a
61 46 24
n/a
90 90 68 33 108 107 88 88 50
4 56 41 19 85 85 63 28 103 102 83 83 45
5 51 36 14 80 80 58 23 98 97 78 78 40
6 46 31 9 75 75 53 18 93 92 73 73 35
7 41 26
n/a
70 70 48 13 88 87 68 68 30
8 36 21 65 65 43
n/a
83 82 63 63 25
9 31 16 60 60 38 78 77 58 58 20
10 26 11 55 55 33 73 72 53 53 15
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
NOTE - Contact your local FTC if more than 85ft of venting is needed.
Table 6A.
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl
Space For Intake Air in Feet
Standard Termination at Elevation 2,001 - 10,000 ft
Number of
90° Elbows
Used
2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 71 30 15
n/a n/a
100 96 53 38
n/a
118 117 98 98 60
2 66 25 10 95 91 48 33 113 112 93 93 55
3 61 20
n/a
90 86 43 28 108 107 88 88 50
4 56 15 85 81 38 23 103 102 83 83 45
5 51 10 80 76 33 18 98 97 78 78 40
6 46
n/a
75 71 28 13 93 92 73 73 35
7 41 70 66 23
n/a
88 87 68 68 30
8 36 65 61 18 83 82 63 63 25
9 31 60 56 13 78 77 58 58 20
10 26 55 51 n/a 73 72 53 53 15
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
NOTE - Contact your local FTC if more than 85ft of venting is needed.
Table 6B.