Table 16 or Table 17 list required pressure switch changes and orice conversion kits at varying altitudes.
The combustion air pressure switches are factory set and require no adjustment.
Table 15.
Manifold and Supply Line Pressure 0-10,000 ft.
Capacity Gas
Manifold Pressure in. w.g.
Supply Line Pressure
in. w.g.
0-10,000 ft.
0-4500 ft. 4501-5500 ft. 5501-6500 ft. 6501-7500 ft. 7501-10000 ft.
All Sizes
Natural 3.5 3.3 3.2 3.1 3.5 4.5 13.0
LP /
Propane
10.0 9.4 9.1 8.9 10.0 11.0 13.0
NOTE: A natural to LP propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation
instruction for the conversion procedure.
Capacity
0-7,500 ft
(0-2,286m)
7,501 - 10,000 ft
(2,286 - 3,048 m)
Natural to LP/Propane
High Altitude Natural Burner
Orice Kit
High Altitude LP/Propane
Burner Orice Kit
045
11K49 73W37 11K44
070
090
110
135
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-
1370 m).
Table 16. Burner Orice Conversion Kits at Varying Altitudes
Capacity
0 - 4500 ft
(0 - 1,371m)
4501 - 7500 ft
(1371 - 2286m)
7501 - 10000 ft
(2286 - 3048m)
045 No Change 11U66 11U69
070 No Change 11U70 11U68
090 No Change 11U70
11U64
110 No Change 11U70
135 No Change 11U70 11U68
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-
1371 m).
Table 17. Pressure Switch Requirements at Varying Altitudes