Service panel
Lock nut
Conduit cover
Conduit
plate
Conduit pipe
3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Remove the service panel.
2) Remove the conduit cover.
3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against
unit with screws.
4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply
cord (K) to the TB support.
5) Loosen the terminal screws, then attach indoor/outdoor unit connecting wire (A) and power
supply cord (K) from the indoor unit correctly to the terminal block. Attach the wires to the
terminal block securely so that the cores cannot be seen, and no external force affects
the connecting section of the terminal block.
6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.
7) Install the conduit cover.
8) Install the service panel securely.
Power supply cord (K)
• Make ground wire a little longer than others.
(More than 3-7/8 in. [100 mm])
• For future servicing, leave some slack in the
connecting wires.
L1
L2
3-2. FLARE CONNECTION
1) Cut the copper pipe as straight as possible with a pipe cutter. (Fig. 1, 2)
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to
avoid getting metal shavings into the piping. (Fig. 3)
5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWVWKHQSXWWKHPRQSLSH
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select
A inch (mm) from the table according to the tool you use.
5) Check
&RPSDUHWKHÀDUHGZRUNZLWK)LJ
,IÀDUHLVGHIHFWLYHFXWRIIWKHVHFWLRQDQGUHSHDWSURFHGXUH
Terminal block
to conduit cover
Power supply cord (K)
Indoor/outdoor unit
connecting wire (A)
TB support
Grounding
terminal
Pipe diameter
inch (mm)
B
inch
(mm)
A inch (mm) Tightening torque
Clutch
type tool
for R410A
Clutch type
tool
for R22
Wing nut
type tool
for R22
ft-lb
(kgf•cm)
N•m
ø 1/4 (6.35)
21/32
(17)
0 to 0.02
(0 to 0.5)
0.04 to 0.06
(1.0 to 1.5)
0.06 to
0.08
(1.5 to 2.0)
10 to 13
(140 to 180)
13.7 to 17.7
ø 3/8 (9.52)
7/8
(22)
25 to 30
(350 to 420)
34.3 to 41.2
ø 1/2 (12.7)
1-1/32
(26)
0.08 to
0.10
(2.0 to 2.5)
36 to 42
(500 to 575)
49.0 to 56.4
ø 5/8 (15.88)
1-5/32
(29)
54 to 58
(750 to 800)
73.5 to 78.4
3. OUTDOOR UNIT INSTALLATION
Lead
wire
5/8 in.
(15 mm)
3-3. PIPE CONNECTION
)DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOHDERYH
:KHQIDVWHQHGWRRWLJKWÀDUHQXWPD\HYHQWXDOO\EUHDNDQGFDXVHUHIULJHUDQWOHDNDJH
• Be sure to wrap insulation around the piping. Direct contact with the bare piping may
result in burns or frostbite.
Indoor unit connection
Connect both liquid and gas piping to indoor unit.
$SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO - RQ WKH ÀDUHG HQGV RI WKH SLSHV'RQRWDSSO\
refrigeration oil on screw threads. Excessive tightening torque will result in damage on
the screw.
7RFRQQHFW¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXWE\KDQG
• Use tightening torque table in (3-2.) as a guideline for indoor unit side joints, and tighten
XVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure
detailed in Indoor unit connection.
• For tightening, use a torque wrench or spanner.
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection on the outdoor unit.
• When piping has to be installed through a ceiling, closet or where the temperature and
KXPLGLW\DUHKLJKXVHDGGLWLRQDO¿HOGVXSSOLHGLQVXODWLRQWRSUHYHQWFRQGHQVDWLRQ
WARNING
When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
Indoor unit
connection
Outdoor unit
connection
Copper
pipe
Fig. 1
Good
90°
Tilted
No good
Fig. 2
Uneven Burred
Fig. 4
Clutch type
Flaring tool
Wing nut type
Fig. 5
Flare nut
Die
Copper pipe
Smooth all around
Even length all around
Inside is shining without any scratches.
Fig. 6
Flare nut Union joint
External thread sideInternal thread side
7LJKWHQWKHÀDUHQXW
with a torque wrench.
Grip the nut on the
union joint with a spanner.
Burr
Copper pipe
Spare reamer
Pipe cutter
Fig. 3