4.3 Error Code: Overview
If an error code appears on the controller, please contact the installation personnel and inform them of the error code, device
model, and serial number (you can find the information on the nameplate of the unit).
Table 4-3 Outdoor unit error code
Error descriptionError code
Manual re-start
required
A01
A11
AA1
Ad1
C21
C26
C28
C2A
1C41
E41
EC1
F31
F41
F62
F63
F6A
F71
F72
F75
F7A
F91
FA1
FC1
Fd1
1L--
1L01
1J--
1J01
P11
P12
P13
P21
P22
P24
P25
NO
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
YES
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
YES
NO
NO
YES
Emergency stop
Indoor unit refrigerant leakage
Inverter driver chip and main control chip mismatch
Refrigerant shut-off device error
Communication error between indoor and outdoor unit
Number of indoor units detected by the outdoor unit has decreased
Number of indoor units detected by the outdoor unit has increased
Communication error between outdoor unit and refrigerant shut-off device
Communication error between main control chip and inverter driver chip
Outdoor ambient temperature sensor (T4) error (open/short)
Refrigerant leakage sensor error
Plate heat exchanger outlet temperature sensor (T6B) error (open/short)
Outdoor heat exchanger temperature sensor (T3) error (open/short)
Inverter module temperature (Tf) protection
Non-inductance resistor temperature (Tr) protection
F62 protection occurs 3 times in 100 minutes
Discharge temperature sensor (T7C) error (open/short)
Discharge temperature (T7C) protection
Compressor discharge insufficient superheat protection
F72 protection occurs 3 times in 100 minutes
Liquid pipe temperature sensor (T5) error (open/short)
Outdoor heat exchanger inlet temperature sensor (T8) error (open/short)
Outdoor heat exchanger outlet temperature sensor (TL) error (open/short)
Compressor suction temperature sensor (T7) error (open/short)
Compressor error. Refer to Table 4-5 for indications of “--”
1L1* error occurs 3 times in 60 minutes. Refer to Table 4-5 for indications of “*”
Fan motor error. Refer to Table 4-6 for indications of “--”
1J1* error occurs 10 times in 60 minutes. Refer to Table 4-6 for indications of “*”
High pressure sensor error
Discharge pipe high pressure protection
Discharge pipe high pressure switch protection
Low pressure sensor error
Suction pipe low pressure protection
Suction pipe low pressure abnormal rise
P22 error occurs 3 times in 100 minutes