Do not install the air conditioner in a
location where flammable gas may leak out.
If the gas leaks out and stays around the air
conditioner, a fire may break out.
When the combination ratio of IDUs is
greater than or equal to 110%, in order to
ensure the capacity of the machine, try to
turn on the indoor units at different time.
The outdoor unit window-shades should be
cleaned periodically to prevent jamming.
This window-shapes is the heat dissipation
outlet of components, if it is jammed, it will
cause the components shorten their service life
spans because of being overheated for an
extended period.
The temperature of refrigerant circuit will
be high. Please
keep the interconnection cable away from
the copper tube.
The sound pressure level is below 70
dB(A).
This appliance is intended to be used by
expert or trained users in shops, in light
industry and on farms, or for commercial
use by lay persons.
1.3 Instructions for Application
Using R32 Refrigerant
The application uses R32 refrigerant.
Appliance shall be installed, operated and
stored in a room that meets special
requirements and has an area limit as shown
in sections 1.3.1.
The appliance shall be stored in a
well-ventilated area where the room size
corresponds to the room area as specified for
operation.
The appliance shall be stored in a room that
does not have continuously operating open
flames (for example an operating gas
appliance) and ignition sources (for example,
an operating electric heater).
1.3.1.1 Unit installation requirements
1.3.1.2 Piping installation requirements
Low temperature solder alloys, such as lead/tin alloys,
are not acceptable for pipe connections.
Reusable mechanical connectors and flared joints are
not allowed indoors.
(EN 60335-2-40 Standard Requirements).
Mechanical connectors used indoors shall comply with
ISO 14903. When mechanical connectors are reused
indoors, sealing parts shall be renewed. When flared
joints are reused indoors, the flaring part shall be
re-fabricated.
Flexible refrigerant connectors (such as connecting
lines between the indoor and outdoor unit) that may
become displaced during normal operations shall be
protected against mechanical damage.
(IEC 60335-2-40 Standard Requirements).
The outdoor unit shall be located in a well-ventilated
location other than the occupied space, such as in the
open air.
For installation of the indoor unit, refer to the
corresponding installation and operation manual.
If an indoor unit is installed in an unventilated area, the
area shall be so constructed that should any refrigerant
leak, it will not stagnate so as to create a fire or
explosion hazard.
1.3.1 System layout requirements
Caution: Risk of fire
Caution: Risk of fire
(for IEC/EN 60335-2-40
except IEC 60335-2-40: 2018)
(for IEC 60335-2-40: 2018 only)
The application uses R32 refrigerant.
Do not use means to accelerate the defrosting
process or to clean, other than those
recommended by the manufacturer.
The appliance shall be stored in a room that
does not have continuously operating ignition
sources (for example: open flames, an
operating gas appliance or an operating electric
heater).
Do not pierce or burn the unit.
Be aware that refrigerants may be odorless.
WARNING
WARNING
WARNING
WARNING
WARNING