2. OPERATIONS
Use the system in the following temperatures to
ensure safe and effective operation. The Operating
range for the air conditioner is shown in Table 2-1.
Table 2-1
2.1 Operating Range
Cooling
Heating
Dehumidification
Outdoor temperature /DB
Indoor temperature /DB
Indoor temperature /WB
Outdoor temperature /DB
Indoor temperature /DB
Outdoor temperature /WB
Model
-15 °C to 52 °C
8/10/12/14/16/18 kW
16 °C to 30 °C
13 °C to 23 °C
Outdoor temperature /DB
Indoor temperature /DB
Indoor temperature /WB
-15 °C to 52 °C
12 °C to 30 °C
9 °C to 23 °C
-20 °C to 30 °C
-20 °C to 16.5 °C
16 °C to 30 °C
2.2 Operation and Performance
2.2.1 Operating System
Run
2.2.2 Cooling and heating operations
The indoor units in the air conditioner can be controlled
separately, but the indoor units in the same system
cannot operate in the heating and cooling modes at the
same time.
When the cooling and heating operation conflict with
each other, the indoor units which are running in cooling
or fan mode will stop and will display the message
standby or no priority on the control panel. Those indoor
units which are running on heating mode will run
continuously.
If the air conditioner administrator has set the running
mode, then the air conditioner cannot run in any mode
other than the mode presented. Standby or no priority
will be displayed on the control panel.
Press the "switch" button on the controller.
Result: The running light turns on and the system starts
to run.
Stop
Press the "switch" button on the controller again.
Result: The running light is now off, and the system
stops running.
Adjust
Refer to the controller user manual for information about
how to set the required temperature, fan speed and air
flow direction.
Repeatedly press the mode selector on the controller to
select the required operation mode.
If the above operating conditions cannot be
met, the safety protection function may be
triggered and the air conditioner may
malfunction.
When the unit operates in "cooling" mode in a
relatively humid environment (relative
humidity higher than 80%), condensation
may occur on the surface of the IDU and
water may drip. In this case, turn the wind
deflector to the maximum air outlet position
and set the fan speed to "High".
Outdoor operating temperature under -5
°C
in
"cooling" mode, the startup capacity of IDUs
must meet at least 30% of ODU capacity.
NOTE
To protect this unit, please turn on the main
power supply 12 hours before you start to
operate this unit.
Once the unit has stopped running, do not
disconnect the power immediately. Wait for at
least 10 minutes.
2.2.3 Features of heating operation
While heating, as the outdoor temperature decreases,
frost may form on the heat exchanger in the outdoor
unit, making it more difficult for the heat exchanger to
heat up the air. The heating capacity will decrease, and
the system will need to be defrosted in order to provide
sufficient heat to the indoor unit. At this point, the control
panel of the indoor unit will show that a defrost
operation is occurring.
Once the unit starts, it takes some time for the room
temperature to rise, as the unit uses a hot air circulation
system to heat the room.
The indoor fan motor will automatically stop running so
as to prevent cold air from coming out of the indoor unit
when the heating operation starts. This process will take
some time, which depends on the indoor and outdoor
temperature. This is not a malfunction.
When there is a drop in the external temperature, the
heating capacity decreases. If this happens, please use
other heating equipment and units at the same time.
(Make sure the room is well ventilated if you are using
equipment that produces fire.) Do not place any
equipment that may produce a fire where the air outlets
of the unit are or below the unit itself.
And need to perform the following operations to prevent
the heating capacity from dropping or prevent cold air
from coming out of the system.
About heating capacity
Defrost operation