Ducting Requirements
Recommended Use only for short-run
installation
Weather Hood
Type
4" DIA
4" DIA
4"
4 inch. (10.2 cm)
4" DIA
2-1/2"
2.5 inch. (6.4 cm)
No. of 90°
elbows
Rigid Metallic Rigid Metallic
0 90 ft. (27.4 m) 60 ft. (18.3 m)
1 60 ft. (18.3 m) 45 ft. (13.7 m)
2 45 ft. (13.7 m) 35 ft. (10.7 m)
3 35 ft. (10.7 m) 25 ft. ( 7.6 m)
Manometer measurements
The static pressure in any exhaust system for best results shall be between
0.3 to 0.8 inches of water column, and cannot be less than 0 under any
circumstances. with installed duct of 4 inch diameter. Measurement must
be done with the empty dryer working with a manometer at the point
where the exhaust duct connects to the dryer. A no-heat setting should be
used. Lint filter must be clean.
If this new dryer is installed into an existing exhaust system you must make
sure:
The exhaust system meets all local, state, and national codes.
That a flexible plastic duct is not used.
To inspect and clean all lint buildup from inside the existing duct.
The duct is not dented or crushed.
The exhaust hood damper opens and closes freely.
13
DRYER
SAFETY
OPERATION
REQUIREMENTS
PARTS AND
FEATURES
INSTALLATION
INSTRUCTIONS
DRYER USE
APPENDIX
DRYER CARE
TROUBLESHOOTING

Bekijk gratis de handleiding van Midea MLTE70N1AWW, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkMidea
ModelMLTE70N1AWW
CategorieWasdroger
TaalNederlands
Grootte5103 MB