18
Floor
>2500 mm
Ceiling
≥A
Capacity(kW)
kW≤3.6
3.6<kW≤7.1
A(mm)
153
189
Panel
Return
air inlet
Air outlet
Louver
Ensure that the airflow in and out of the indoor unit is reasonably organized to form an air circulation in the room.
Prevent the air conditioner from blowing directly at the human body.
Keep the air-conditioning return air away from direct exposure to the sun in the room.
The indoor unit should not be lifted in the places like load-bearing beams and columns that affect the structural safety
of the house.
The wired controller and the indoor unit should be in the same installation space, otherwise, the sampling point
setting of the wired controller needs to be changed.
It is recommended to install the air conditioner according to the design drawing of the HVAC engineer.
The selection principle for the installation site is as follows:
Recommended Installation Sites
Choose a site that fully complies with the following conditions and user requirements to install the
air conditioning unit:
There is enough space for installation and maintenance.
The ceiling is level, and the structure is strong enough to support the indoor unit. If necessary, take measures to
reinforce the unit's stability.
Airflow in/out of the unit is not obstructed.
It is easy to supply airflow to every corner of the room.
It is easy to drain for water drain piping.
There is no direct heat radiation.
Avoid installation in narrow spaces or where there are more stringent noise requirements.
The indoor unit needs to be installed at a position greater than 2.5m and less than 3.5m from the ground.
The length of the piping between the indoor and outdoor units is within the permitted range. Refer to the Installation
and Operation Manual attached with the outdoor unit.
NOTE
In case of conditions in the ceiling exceed 30℃ and relative humidity of 80%, or when fresh air is inducted into the
ceiling, the additional insulation is requried(minimum 10 mm thickness polyethylene foam).