Midea H1-(5-20)-E0 handleiding
Handleiding
Je bekijkt pagina 26 van 32

6.2 Daily Maintenance of the System
To ensure that the battery can operate properly for a long term, you are advised
to perform routine maintenance on it as described in this chapter.
Before cleaning the system, connecting cables, and ensuring the grounding
reliability, power o the system.
ATTENTION
6.3 Battery Module Storage Requirements and Power Supply
Battery Module Storage Requirements:
• Environment temperature: -10°C ~45°C
• Recommended storage temperature:20°C ~30°C
• Storage relative humidity range: 5%~80%.
• Store in a dry, clean, and ventilated environment, away from direct sunlight.
• When storing the battery module, place it correctly. Do not put the battery
module upside down or on its side.
• If the energy storage module is stored for a long time, replenish the power
supply periodically.
Recharge Requirements during Normal Storage
When the battery is stored for a long time, you need to perform regular
maintenance. If the storage time is close to that shown in the following table,
arrange supplementary power supply in time.
Check Item
Check Method
Maintenance
Interval
System
cleanliness
Check periodically that the heat sinks
are free from obstacles and dust.
Once every 6 to
12 months
System
running
status
Check that the battery is not damaged or
deformed.
Check that the battery does not generate
abnormal sound when it is in operation.
Check that the battery parameters are cor-
rectly set when the battery is running.
Once every 6
mon
ths
Electrical
connection
Check that cables are secured.
Check that cables are intact, and that in
particular, the parts touching the metallic
surface are not scratched.
Check that unused DC input terminals, bat-
tery terminals, and COM ports are locked by
watertight caps.
The first inspection
is 6 months after the
initial commission-
ing.From then on,
the interval can be 6
to 12 months.
Grounding
reliability
Check that ground cables are securely
connected.
The first inspection
is 6 months after the
initial commission-
ing.From then on,
the interval can be 6
to 12 months.