USING THE BROWSER-BASED INTERFACE
Page 32
• View the Status field to see the current sequence state. With sequencing disabled, the
field shows “Not Sequenced”. If sequencing has not been initiated or if any sequenced
outlet has changed state, the field shows “Not Sequenced”. Otherwise, one of the
following statuses appear in this field:
o Sequencing ON in Progress
o Sequencing ON Complete
o Sequencing OFF in Progress
o Sequencing OFF Complete
4. Use the Initiate Sequence buttons to start a sequence as follows:
• Click On or Off to initiate a sequence to activate or deactivate the outlets (depending on
the initial state of the outlets on your RackLink unit).
After selecting On or Off, then adjust the delay.
• In the Delay field, enter a delay value (in seconds) for the amount of time you wish to
elapse between each controlled outlet in the sequence. The set delay time applies to all
sequenced outlets and can be set from 0 – 255 seconds.
• Click Initiate after setting the delay.
Configuring Outlet Controls
To configure outlet controls:
1. Install and launch your RackLink Discovery software and connect to a RackLink device.
For more information, see “Installing the Device Discovery Software and Accessing a
Connected RackLink’s Browser-Based Interface” on page 13.
2. Enter the credentials for the account you wish to use. For more information, see “Logging in to
the Browser-Based Interface” on page 27.
The Dashboard appears.
3. At the top of the Outlet Control section of the screen, the outlet drop-down provides the
following viewing choices:
• Show All Outlets
• Show In Sequence Outlets Only
• Show AutoPing Enabled Outlets Only
• Show Controlled Outlets Only
Bekijk gratis de handleiding van Middle Atlantic RLNK-410R-IEC-NS, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.