Middle Atlantic ERK-4425-AV handleiding
Handleiding
Je bekijkt pagina 5 van 8

Load Ratings: 2,500 lbs. load rating
Added Weight (Loading): Total added weight should be distributed as follows:
• 1/2 of the total added weight (at a minimum) placed in the bottom third of the enclosure
• 1/4 of the total added weight (at a maximum) palced in the middle third of the enclosure
• 1/4 of the total added weight (at a maximum) placed in the top third of the enclosure
• Enclosure is intended for use in ambient temperatures of 32°F (0°C) to 140°F (60°C).
• Front Door (Optional): Full width door can be hinged on the left or right of the rack frame. Ensure
door is bonded to enclosure frame. See Grounding and Bonding on page 6 for details.
• Rear Door: Full width door can be hinged on the left or right of the rack frame. Ensure
door is bonded to enclosure frame. See Grounding and Bonding on page 6 for details.
.
Page 5
SPECIFICATIONS
GENERAL INFORMATION
Heights: 10 RU to 44 RU (each RU = 1.75”)
Widths: 22”
Depths: 20”, 25” and 28”