Technical Manual Presence Detector SCN-x360xx.03
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Telephone: +49-2263-880 • knx@mdt.de • www.mdt.de
13
13
130
Constant light
Switch On/Off
1 Bit
X
X
131
Constant light
Dimming relative
4 Bit
X
X
132
Constant light
Dimming absolute
1 Byte
X
X
134
Constant light
Lock
1 Bit
X
X
135
Constant light
Scene control
1 Byte
X
X
136
Constant light
Dimming absolute output middle
1 Byte
X
X
X
137
Constant light
Dimming absolute output wall
1 Byte
X
X
X
138
Constant light
Dimming absolute output window
1 Byte
X
X
X
139
Constant light
Status
1 Bit
X
X
X
140
Temperature
Measured value
2Bytes
X
X
X
Table 1: Communication objects Standard settings
The tables above show the default settings. The priority of the individual communication objects and
the flags can be adjusted by the user as required. The flags assign the communication objects their
respective tasks in the programming. "C" stands for communication, "R" for reading, "W" for writing,
"T" for transmitting and "U" for updating.