Technical Manual – Presence Detector SCN-P360D1.01
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
16
16
The following table shows the available settings for these parameters:
ETS-Text
Dynamic range
[Default value]
Comment
Object type for output - light
• Switching
• Dimming absolute
• Scene
Adjustment oft p16-he switching
object of the light group
output
Object type for output –
climate(HCV)
• Switching
• Send value
• Scene
Adjustment oft p16-he switching
object of the HCV output
Object value on day
for On
• On/Off
• 0-100% [100%]
• Scene 1-32 [5]
Adjustment of the sending at
this state
Object value on day
for Off
• On/Off
• 0-100% [0%]
• Scene 1-32 [6]
Adjustment of the sending at
this state
Object value on night
for On
• On/Off
• 0-100% [100%]
• Scene 1-32 [7]
Adjustment of the sending at
this state
Object value on night
for Off
• On/Off
• 0-100% [0%]
• Scene 1-32 [8]
Adjustment of the sending at
this state
Use 2. switch object at night
(only at light groups and
object type switch)
• Yes
• No
shows a second switching
object fort p16-he night mode, e.g.
for switching an orientation
light
Standby/Orientationlight
(only at light groups and
object type dimming
absolute)
• used
• not used
Activation of a standby
function, which starts after
expiration of the follow-up
time
Standby time on
day/night
• no delay
• 1s – 60min
Adjustment of the duration of
the standby time
Standby dimming
value on day/Night
1- 100%
[1%]
Adjustment of the dimming
value for the standby function
Switching object send at
(only at object type switching)
• send nothing
• only ON
• only OFF
• ON and OFF
Sendefilter für das
Ausgangsobjekt
Cyclical sending of object
value ON
• not used
• 1min – 60min
Activation of cyclic sending
External input reacts on
• send nothing
• only ON
• only OFF
• ON and OFF
Input filter for the object
External Input – light group
1/2/HCV
Idle time after swtitch off
1s – 60s
[10s]
Time, which must expire after
swiotching off for detecting a
new movement
Table 6: Communication object setting presence function