MDT SCN-LED55.01 handleiding

34 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 28 van 34
Technical Manual
LED-Indicator SCN-LED55.01/SCN-GLED1x.01
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-880 • Fax: +49-2263-4588 knx@mdt.de • www.mdt.de
28
28
The following table shows the available settings for this mode:
ETS-text
Dynamic range
[default value]
comment
Mode
Byte=>Bit
adjusted Mode: Byte =>Bit
Threshold
1-255
[1]
Setting from when the output is
switched.
If the byte value is less than the set
value, the output sends a 1 signal at
normal setting.
Output level at input value >=
Threshold
normally: Output
value = 1
inverted: Output
value = 0
Inverted/normal output of the output,
normally: Output value 1, if input is
greater than/equal the adjusted
threshold
inverted: Output value 1, if input is
smaller than threshold
Table 24: Converter, Mode: Byte=>Bit
The following table shows the objects of the converter for the mode byte => bit (here for the
converter module A):
Number
Name
Length
Usage
116
Input value A1
1 Byte
Value of the size 1 Byte which should be converted
119
Output value A1
1 Bit
Converted value
Table 25: Communication object converter, Mode: Byte=>Bit