Reset time:
The reset time represents the I-component of a control. This leads to an integral approach of the
actual value to the setpoint. A short reset time means a strong I component.
A short reset time causes the control value to quickly approach the control value set according to
the proportional range. A long reset time, on the other hand, causes a slow approach to this value.
The following figure illustrates the interrelationships of PI control:
Figure 19: Diagram – Principle of the PI-Control
The following communication objects are available for this:
Number
Name/Object function
Length
Usage
37
Air quality control –Preset setpoint
2 Byte
Specification of a new absolute setpoint
38
Air quality control –Current setpoint
2 Byte
Display of the currently set setpoint
52
Air quality controller –
Output control value
1 Byte
Sending the control value
57
Day / Night –
Day = 1 / Night = 0, Night = 1 / Day = 0
1 Bit
Switchover between Day and Night
Operation
Table 25: Communication objects – PI controller
For more information on the parameters that are not described in detail, see the following chapters:
4.3.2.1 General parametersFehler! Ungültiger Eigenverweis auf Textmarke.
4.3.2.7 Send setpoint/output cyclically