Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
29
29
4.3.2.2 Specific settings – Step controller Bit coded
The following illustration shows the specific settings for this type of controller:
Figure 14: Settings – Step controller Bit coded
The following table shows the specific settings for this controller type:
ETS-Text
Dynamic range
[Default value]
Comment
Minimum level for
„Day“
Level 0 – Level 4
[Level 0]
Defines the minimum or maximum level
to be switched in "Day" or "Night"
mode.
Maximum level for
„Day“
Level 0 – Level 4
[Level 4]
Minimum level for
„Night“
Level 0 – Level 4
[Level 0]
Maximum level for
„Night“
Level 0 – Level 4
[Level 4]
Threshold level 1
Threshold level 2
Threshold level 3
Threshold level 4
400 … 2000 ppm
[600]
[800]
[1000]
[1200]
50 … 500
[80]
[160]
[240]
[320]
Setting range of the threshold values at
which switching is to take place.
Unit (ppm/IAQ) depending on the
selection in "Controller actual value".
Hysteresis in
• percent
• ppm
Setting with which unit the hysteresis is
determined.
Selection depends on the setting in
"Controller actual value".
• percent
• IAQ
Hysteresis
0 … 20 %
[10 %]
Setting the hysteresis in „percent“.
10 … 500 ppm
[50 ppm]
Setting the hysteresis in „ppm“.
0 … 50
[5]
Setting the hysteresis when "IAQ" is
selected.
Table 18: Settings – Step controller Bit coded