Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
29
29
4.3.2.2 Specific settings Step controller Bit coded
The following illustration shows the specific settings for this type of controller:
Figure 14: Settings Step controller Bit coded
The following table shows the specific settings for this controller type:
ETS-Text
Dynamic range
[Default value]
Comment
Minimum level for
„Day“
Level 0 Level 4
[Level 0]
Defines the minimum or maximum level
to be switched in "Day" or "Night"
mode.
Maximum level for
„Day“
Level 0 Level 4
[Level 4]
Minimum level for
„Night“
Level 0 Level 4
[Level 0]
Maximum level for
„Night“
Level 0 Level 4
[Level 4]
Threshold level 1
Threshold level 2
Threshold level 3
Threshold level 4
400 … 2000 ppm
[600]
[800]
[1000]
[1200]
50 … 500
[80]
[160]
[240]
[320]
Setting range of the threshold values at
which switching is to take place.
Unit (ppm/IAQ) depending on the
selection in "Controller actual value".
Hysteresis in
percent
ppm
Setting with which unit the hysteresis is
determined.
Selection depends on the setting in
"Controller actual value".
percent
IAQ
Hysteresis
0 … 20 %
[10 %]
Setting the hysteresis in percent“.
10 … 500 ppm
[50 ppm]
Setting the hysteresis in „ppm“.
0 … 50
[5]
Setting the hysteresis when "IAQ" is
selected.
Table 18: Settings Step controller Bit coded