MDT SCN-CO2MGS01.02 handleiding

77 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 19 van 77
Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
19
19
4.2.3 Temperature measurement
The following settings are available:
Figure 7: Settings Temperature measurement
The table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Send measured value
on change
not active
active
Setting whether the measured
value should be sent on change.
Send measured
value on change of
0.1 … 2 K
[0.1 K]
Setting at which change the
measured value should be sent.
Only visible if "Send measured
value on change" is activated.
Send measured value
cyclically
not active
1 min 60 min
Setting whether and at what
interval the measured value is sent
cyclically.
Messages
not active
active
Activation of the message function.
Upper message
value
20 … 45 °C
[28 °C]
Setting range of the upper/lower
message value.
Only visible when parameter
"Messages" is activated.
Lower message
value
3 … 30 °C
[18 °C]
Calibration value for
internal sensor
-10 … 10 K
[0 K]
Adjustment for internal sensor.
Sensor
internal/external
100% internal
90 % internal/ 10 % external
80 % internal/ 20 % external
10 % internal/ 90 % external
100 % external
maximum value
Setting the weighting between
internal and external sensor.
Table 11: Settings Temperature measurement

Bekijk gratis de handleiding van MDT SCN-CO2MGS01.02, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkMDT
ModelSCN-CO2MGS01.02
CategorieNiet gecategoriseerd
TaalNederlands
Grootte14681 MB