Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
17
17
4.2.2 VOC measurement
The following settings are available:
Figure 6: Settings VOC measurement
The table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Measured value output
in
ppm
IAQ Index (Indoor Air
Quality Index)
Setting for how the measured value is
to be output.
IAQ Index description
Information about the classification of
the IAQ index (Indoor Air Quality
Index).
Displayed when "Measured value
output in" is selected as "IAQ Index".
Send measured value
on change
not active
active
Setting whether the measured value
should be sent on change.
Send measured
value on change of
10 … 500 ppm
[20]
Setting at which change the measured
value should be sent.
Unit depends on the selection of
"Measured value output".
Only visible if "Send measured value
on change" is activated.
1 … 50
[5]
Send measured value
cyclically
not active
1 min 60 min
Setting whether and at what interval
the measured value is sent cyclically.
Messages
not active
active
Activation of the message function.
Upper message
value
100 … 5000 ppm
[2000]
Setting the upper signal value.
Visible when "Messages" is active.
Unit depends on the selection of
"Measured value output".
Setting the lower signal value.
0 … 500
[200]
Lower message
value
100 … 5000 ppm
[1000]
0 … 500
[50]