4.2.1 CO2 measurement
The following settings are available:
Figure 5: Settings – CO2 measurement
The table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Send measured value
on change
▪ not active
• active
Setting whether the measured
value should be sent on change.
Send measured
value on change of
10 … 500 ppm
[20]
Setting at which change the
measured value should be sent.
Only visible if "Send measured
value on change" is activated.
Send measured value
cyclically
not active
1 min – 60 min
Setting whether and at what
interval the measured value is sent
cyclically.
Messages
▪ not active
• active
Activation of the message function.
Upper message
value
400 … 2000 ppm
[1500 ppm]
Setting range of the upper/lower
message value.
Only visible when parameter
"Messages" is activated.
Lower message
value
400 … 2000 ppm
[500 ppm]
Calibration value for
internal sensor
-500 … 500 ppm
[0 ppm]
Adjustment for internal sensor.
Sensor
internal/external
▪ 100% internal
▪ 90 % internal/ 10 % external
▪ 80 % internal/ 20 % external
▪ …
▪ 10 % internal/ 90 % external
▪ 100 % external
▪ maximum value
Setting of the weighting between
internal and external sensor.
Table 7: Settings – CO2 measurement