MDT SCN-CO2MGS.02 handleiding
Handleiding
Je bekijkt pagina 28 van 78

Technical Manual
CO2 / VOC Combi Sensor 55 [SCN-CO2MGS.02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
28
28
Air quality control with humidity increase by…
The parameter is only displayed if a selection is made with "+ Humidity" as "Controller actual value".
Here you can set by which level (" Step controller") or by which control value (PI controller) the air
quality control is to be raised as soon as a certain threshold value for the air humidity is exceeded.
This value is determined with the setting "Threshold for exceeding the humidity".
The "Follow-up time after falling below" defines the minimum time by which the threshold value
must be fallen below to return to the current control.
The following table shows the available communication objects:
Number
Name/Object function
Length
Usage
39
Air quality controller –
CO2 Input 1, VOC Input 1
2 Byte
Input of an external measured value.
DPT depending on the set parameter.
40
Air quality controller –
CO2 Input 2, VOC Input 2
2 Byte
Input of an external measured value.
41
Air quality controller –
CO2 Input 3, VOC Input 3
2 Byte
DPT depending on the set parameter.
42
Air quality controller –
CO2 Input 4, VOC Input 4
2 Byte
Input of an external measured value.
43
Air quality controller –
CO2 Input 5, VOC Input 5
2 Byte
DPT depending on the set parameter.
44
Air quality controller – CO2 Input 6,
VOC Input 6, Humidity Input 1
2 Byte
Input of an external measured value.
45
Air quality controller – CO2 Input 7,
VOC Input 7, Humidity Input 2
2 Byte
DPT depending on the set parameter.
46
Air quality controller – CO2 Input 8,
VOC Input 8, Humidity Input 3
2 Byte
Input of an external measured value.
47
Air quality controller – CO2 Input 9,
VOC Input 9, Humidity Input 4
2 Byte
DPT depending on the set parameter.
48
Air quality controller – CO2 Input 10,
VOC Input 10, Humidity Input 5
2 Byte
Input of an external measured value.
Table 17: Communication objects – Air quality controller: General parameters
Bekijk gratis de handleiding van MDT SCN-CO2MGS.02, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | MDT |
| Model | SCN-CO2MGS.02 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 0 MB |