MDT SCN-BWM55T.G2 handleiding
Handleiding
Je bekijkt pagina 51 van 67

MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany
Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt-group.com
51 / 67
Technical Manual
Motion Detector/Automatic Switch 55/63 [SCN-BWM55/63(T)(06).x2]
State 07/2025 - Version 1.4
4.3.2.5 Basic function: Send state
Single-button function
Withthisfunction,xedvaluescanbesentforapressedbutton(risingedge)andareleasedbutton(falling
edge).
The following table shows the available settings::
ETS Text
Dynamic range
[Default value]
Comment
Value for pressed button ■ OFF
■ ON
Denesthesendbehaviourofthebutton.
Value for released button ■ OFF
■ ON
Denesthesendbehaviourofthebutton.
Cyclic sending ■ not active
■ active
Setting whether the value is sent cyclically.
Send cyclically every ... 1 s ... 3000 s
[300 s]
Setting the sending interval.
Only if “Cyclic sending” is active.
Send state after bus
power return
■ not active
■ active
Setting to specify whether the current state
is sent after bus power return.
Table 60: Settings – Single-button function: Send state
The following table shows the associated communication objects:
No. Name/Object function Length Usage
131 Button left – Send state 1 Bit Sends the respective value when the button is
pressed and released.
+5 Button right ...
Table 61: Communication objects – Single-button function: Send state