4.2.1.3 Forced guidance/Lock object
Light channel
HVAC channel
The following table shows the available settings:
ETS Text
Dynamic range
[Default value]
Comment
Forced guidance or
lock object
■ forced guidance object (2 Bit)
■ lock object
■ lock object and lock object ON
Setting whether a forced guidance object
or which lock objects should be used.
Action on locking ■ lock motion (lock current state)
■ switch ON
■ switch OFF
Denesthestatusthatistobesentduring
locking.
Only if “Lock object” is selected.
Fallback of forced
guidance/lock
(General setting)
■ not active
■ active
Setting whether the channel should react
to “Fallback forced guidance/lock” in the
menu “General settings”.
Table 18: Settings – Forced guidance / Lock object
Functional principle:
The device can be overridden with the forced guidance/lock object and call up a certain status.
The forced guidance object knows 3 possible states:
■ Forced guidance ON (control = 1, value = 1)
The command for “ON” is sent unconditionally to the output object. The evaluation is then stopped and
the release time for forced guidance begins. If nothing is received on the forced guidance object after
the release time has expired, normal operation is resumed.
■ Forced guidance OFF (control = 1, value = 0)
The command for “OFF” is sent unconditionally to the output object. The evaluation is then stopped
and the release time for forced guidance begins. If nothing is received on the forced guidance object
after the release time has expired, normal operation is resumed.
■ Forced guidance AUTO (control = 0, value = 0)
Deactivate forced guidance. The detector will resume to normal operation.
As an alternative to the forced guidance object, 1 or 2 locking objects of size 1 Bit can be displayed.
3differentstatescanbeconguredforthelockobject:
■ Lock motion (lock current state)
The channel is locked in its current state and remains locked until the locking process is deactivated.
■ Switch ON
The channel switches ON and remains in this state until the locking process is deactivated.
■ Switch OFF
The channel switches OFF and remains in this state up to when the locking process is deactivated.
By activating the object “Lock object ON”, the channel sends the output value ON and remains in the ON
state until the locking process is deactivated.