Monitoring time slot
Presencemustbedetectedatleastoncewithinaspeciedtimeinoneormoremonitoringtimeslotin
order to switch the channel output. This avoids the output being switched if there is only a short detection.
The “Number of monitoring time slots” and the “Length of the monitoring time slot” can be set
individually.
Follow-up time
This parameter describes the time that elapses after the last detection of a movement until the output is
switched off. The follow-up time can be set differently for Day/Night. For example, with a follow-up time of
3 minutes, the light would be switched on for at least 3 minutes if motion was detected. Each new
detection leads to a re-triggering and thus a restart of the follow-up time.
Object “Lock motion detection”
The “Lock motion detection” object, which is permanently displayed, deactivates motion detection for this
HVAC channel. In comparison to a lock via the lock object, the channel can still be operated manually via
internal and external button functions.
The following table shows the associated communication objects:
No. Name/Object function Length Usage
66 HVAC channel - Input –
Status of actuator channel
1 Bit Response from the actuator’s status output.
67 HVAC channel - Input –
Lock motion detection
1 Bit Motion detection lock to this channel.
73 HVAC channel - Input –
Follow-up time 10 - 65000 s
2 Byte Sets the follow-up time via an external object.
Table 17: Communication objects – Basic settings: HVAC channel