Technical Manual – Push Button Smart 55/63
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
63
63
4.6.10 Blinds/Shutter
Single-Button function
Two-Button function
The blinds/shutter function is used to control shutter actuators, which can be used for the
adjustment and control of blinds/shutters.
The following figure shows the available settings (here: Two-button function):
Figure 33: Settings – Blinds/Shutter
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Key assignment (1/2)
▪ Up/Down
▪ Down/Up
Only with two-button function!
Setting the key assignment
(upper/left or lower/right key) for
the up/down function
Operation function
▪ Long=Up/Down (or “move”)/
Short=Stop/slats open/close
▪ Short=Up/Down (or “move”) /
Long=Stop/slats open/close
▪ Short=Up/Down/Stop
(MDT Single Object Control)
▪ Short=Up/Down/Stop /
Long=Central object
(MDT Single Object Control)
Setting the concept of how to
operate with long/short buttons.
Functions with "MDT Single
Object Control" only available
with two-button function!
Time for long keypress
Basic setting
0,1 s – 30 s
Setting of an individual time from
when a long keystroke is
detected
Group control extra
long
▪ not active
▪ active
Activation of a further function
with extra long keystroke
Time for extra-long
keypress
0,1 s – 30 s
[2,0 s]
Setting of an individual time from
when an extra long keystroke is
detected
Table 53: Settings – Blinds/Shutter