MDT BE-TAL55B206.01 handleiding

63 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 36 van 63
MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany
Telephone: +49 (0) 2263 880 · knx@mdt.de · www.mdt.de
36 / 63
Technical Manual
Push Button Lite 55/63/Basic [BE-TALxxxx.x1]
State 09/2024 - Version 1.4
Lower/Upper Limit
The value can be moved within these limits. The function will neither fall below the lower limit nor exceed
the upper limit.
Step width
The step width indicates the distance between the values when shifting values. If the value 10 % was sent
during the previous transmission, the value 20 % will be sent with the next “up” command, with a set step
width of 10 %.
Repeated sending with pressed button
This function allows the value to be increased or decreased for as long as the respective button is pressed
or the upper/lower limit is reached.
No. Name/Object function Length Usage
0 PB1/2: – Percent value, Decimal value 1 Byte Send the value to be shifted.
3 PB1/2: – Status:
Percent value, Decimal value
1 Byte Receive the status value.
Table 20: Communication objects – Send values – Subfunction: Shift value