Technical Manual
Push Button 55 / Plus 55 / Plus TS 55 [BE-TA55xx(06).x2]
State 07/2025 - Version 1.3
The setting “Send measured value cyclically” can be used to set the intervals at which the sensor sends
its current temperature value. The cyclical transmission function can be activated or deactivated
independently of the setting “Send measured value on change of”. Measured values are also sent if the
sensor has not detected a change. If both parameters are deactivated, a value is never sent.
The setting “Send measured value on change of ...” can be used to set at which change the sensor sends
its current measured value. If the setting is “not active”, the sensor does not send a value, no matter how
large the change is.
With the parameter “Calibration value for internal sensor” a correction value can be entered. This is used
to increase/decrease the actual measured value. This setting makes sense if the sensor has been installed
in an unfavourable location, e.g. above a radiator or in a draught area. The temperature sensor sends the
corrected temperature value when this function is activated.
Two messages can be output via “Temperature for upper message value” and “Temperature for lower
message value” when activated. Both signalling functions each have a separate communication object.
Principle:
If the maximum value is exceeded, a “1” is sent. If the value falls below it, a “0” is sent.
If the value falls below the minimum value, a “1” is sent. If it is exceeded, a “0” is sent.
The following table shows the associated communication objects:
No. Name / Object function Length Usage
* 38/62/86/110 Temperature – Send measured
value
2 Byte Sends the current temperature
* 39/63/87/111 Temperature –
External sensor - Input
2 Byte Reception of an externally measured
temperature.
* 40/64/88/112 Temperature –
Maximum value exceeded
1 Bit Sending the status for the upper
message value.
* 41/65/89/113 Temperature –
Minimum value fallen below
1 Bit Sending the status for the lower
message value.
Table 44: Communication objects – Temperature
* Object numbers depend on the device version (number of buttons).