4.2 Button functions - General
The table shows the available settings:
ETS Text
Dynamic range
[Default value]
Comment
Buttons 1/2 (top left / right)
Buttons 3/4 (2. line left / right)
Buttons 5/6 (3. line left / right)
Buttons 7/8 (bottom left / right)
■ not active
■ single-button function
■ two-button function
Setting the functions for the
respective button pair
Reaction time on keypress ■ fast
■ medium
■ slow
Setting the reaction time or debounce
time for the buttons.
Time for long keypress
(Basic setting)
0,1 s – 30,0 s
[0,4 s]
Setting from when a long keypress is
detected.
Table 8: Settings – Button functions
It is determined in advance how a pair of buttons is to be activated and used.
With the “single-button function”, only one button is used for one function.
With the “ two-button function”, 2 buttons are always used for one function and the operating concept
works like a rocker. It is possible to specify for each button which value (on/off, up/down, brighter/darker,
etc.) it is to send.
A corresponding time can be set via “Time for long keypress (basic setting)”.
Note: This time is the basic setting for all buttons.