4.2 Button functions - General
The table shows the available settings:
ETS Text
Dynamic range
[Default value]
Comment
Buttons 1/2 (top left / right)
Buttons 3/4 (2. line left / right)
Buttons 5/6 (3. line left / right)
Buttons 7/8 (bottom left / right)
not active
single-button function
two-button function
Setting the functions for the
respective button pair
Reaction time on keypress fast
medium
slow
Setting the reaction time or debounce
time for the buttons.
Time for long keypress
(Basic setting)
0,1 s – 30,0 s
[0,4 s]
Setting from when a long keypress is
detected.
Table 8: Settings – Button functions
It is determined in advance how a pair of buttons is to be activated and used.
With the “single-button function, only one button is used for one function.
With the “ two-button function, 2 buttons are always used for one function and the operating concept
works like a rocker. It is possible to specify for each button which value (on/off, up/down, brighter/darker,
etc.) it is to send.
A corresponding time can be set via “Time for long keypress (basic setting)”.
Note: This time is the basic setting for all buttons.