Standard Settings – Temperature
No. Name Object Function Length C R W T U
* 38/62/86/110 Temperature Send measured value 2 Byte
■ ■ ■
* 39/63/87/111 Temperature External sensor - Input 2 Byte
■ ■
* 40/64/88/112 Temperature Maximum value exceeded 1 Bit
■ ■ ■
* 41/65/89/113 Temperature Minimum value fallen below 1 Bit
■ ■ ■
Table 4: Communication objects – Standard settings: Temperature
* Temperature objects always come after the buttons in the object list. This means that the object numbers
are dependent on the device version.
2 gang Push Button from object no. 38
4 gang Push Button from object no. 62
6 gang Push Button from object no. 86
8 gang Push Button from object no. 110
Standard Settings – General objects
No. Name Object Function Length C R W T U
* 37/61/85/109 LED Orientation light Switch 1 Bit
■ ■
* 42/66/90/114 In operation Output 1 Bit
■ ■ ■
Table 5: Communication objects – Standard settings: General objects
* General objects are at the end of the object list. This means that the numbers depend on the number of
buttons.
2 gang Push Button from object no. 37
4 gang Push Button from object no. 61
6 gang Push Button from object no. 85
8 gang Push Button from object no. 109
The table above shows the preset default settings. The priority of the individual communications objects
and the flags can be adjusted by the user as required. The flags assign the communication objects their
respective tasks in programming, where C stands for communication, R for read, W for write, T for transmit
and U for update.