Technical Manual
Blind Push Button Smart 55 BE-JTA5504.01
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
13
13
4 Reference-ETS-Parameter
4.1 General Settings
The following picture shows the menu for the general settings:
Figure 3: General Settings
The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Startup time
2 240 s
[2 s]
Sets the time between restart and
functional start-up of the device
Send „Operation“ cyclically
not active
1 min 24 h
Setting whether and at what
interval a cyclical "In operation"
telegram should be sent.
Value for Day/Night
Day = 1 / Night = 0
Day = 0 / Night = 1
Sets the polarity for Day / Night
switchover
Behavior after bus power return
Time/Date
no request
request
Setting whether the values/objects
should be requested automatically
on bus voltage return.
Day/Night object
no request
request
Status/Values for toggle
no request
request
Polarity Shading
lock at value 1
enable at value 1
Setting whether the Shading
should be enabled or disabled with
a "1".
Language Display
German
English
Setting the language for texts in
the display
Table 5: General Settings