Technical Manual
Glass Push-button II Smart & Push-button Smart 86 [Series .02]
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
29
29
4.2.3.3 Messages
The following picture shows the available settings for messages:
Figure 12: Settings – Messages
The following table shows the settings for the messages:
ETS-Text
Dynamic range
[Default value]
Comment
Message 1-4 (1 Bit)
▪ not active
▪ active
Activation of message 1-4.
Message 1 (highest priority)
Text
any text
[up to 15 bytes allowed]
Displayed text when the message
is triggered.
Display time
▪ not active
▪ until button is pressed
▪ 1 s – 8 h
Setting how long the message
should be displayed.
Message 5 (14 Byte)
(lowest priority)
▪ not active
▪ active
Activation of the message via the
14-byte object.
Message 5 has the lowest priority
of all messages.
Display time
▪ not active
▪ until button is pressed
▪ 1 s – 8 h
Setting how long the message
should be displayed.
Resetting the message via
object
▪ not active, only keypress
and display time
▪ active, and with value “0” via
objects “Message (1-4)”
Setting when the message should
be taken back.