6 VC-Strip™ Family Safety and Installation Guide
Each time you reach (a) the maximum permitted number of modules in one chain, or (b) the PSU
output’s maximum power rating – whichever you reach first – you must create a new chain of modules
that is connected to a new 48 VDC power output.
If you supply a chain of VC-Strip modules with DC power from a generic 48 VDC external PSU and the
DC output used does not have constant overcurrent protection that limits current to 8 A, install an inline
fuseholder with a 7.5 A or 8 A fuse on the circuit that you connect to that DC output.
Provide a means of locking out AC mains power that allows power to the installation to be shut down and
made impossible to reapply, even accidentally, during work on the installation.
Shut down power to the installation during service and when it is not in use.
Before applying power to the installation, check that all power distribution equipment and cables are in
perfect condition and rated for the current requirements of all connected devices.
Isolate the installation from power immediately if any product, power cable or power plug is in any way
damaged, defective or wet, or if it shows signs of overheating.
Do not expose the VC-Strip to rain or moisture.
PROTECTION FROM BURNS AND FIRE
The VC-Strip is cooled by convection. Provide free airflow and a minimum clearance of 10 mm (0.4 in.)
around modules. Monitor the VC-Strip’s temperature by calling up temperature readouts on the P3
System Controller. If any of the product temperature readouts exceed the levels given in Table 1 on page
5, provide fan assistance to give active cooling to the installation.
Do not operate the VC-Strip if the ambient temperature (Ta) exceeds 45° C (113° F).
Do not modify the VC-Strip in any way not described in this manual or install other than genuine Martin
parts. Use only accessories approved by Martin.
PROTECTION FROM INJURY
When installing the VC-Strip above ground level, ensure that the installation hardware and supporting
structure can hold at least 10 times the weight of all the devices they support.
In an overhead installation or where the VC-Strip may cause injury if it falls:
- block access below the work area and work from a stable platform whenever installing, servicing or
moving the VC-Strip, and
- as soon as work is completed, check that all hardware and components are securely in place and
fastened to supporting structures.
Type of VC-Strip module in
chain
Maximum permitted
number of modules in one
chain
Wattage per VC-Strip
module
VC-Strip 32x1 15 45 8 W
VC-Strip 16x1 15 63 4 W
VC-Strip 16x1 25 45 8 W
VC-Strip 8x1 25 63 4 W
VC-Strip 16x1 30 45 8 W
VC-Strip 8x1 30 63 4 W
VC-Strip 8x1 60 63 4 W
VC-Strip 4x1 60 63 2 W
Table 3: Maximum number of VC-Strip modules per 48 VDC external PSU