Fig. 160
u
Carry out action steps according to the illustration.
Fig. 161
Fig. 162
u
Carry out action steps according to the illustration.
w
The simulation has been performed.
w
Connected safety devices should have triggered.
6.2.25 Alarm forwarding
This function enables you to set to have one or several
alarms to be forwarded to an external alarm receiver.
Here, the alarm receiver is connected to the applian‐
ce’s potential-free alarm output. (see 7.3 Interfaces)
You can select from the following settings:
-
Alarm type:
Door alarm
Temperature alarm
Door alarm and temperature alarm
All
-
Confirm:
Yes: The alarm is confirmed on the appliance and
the externally connected receiver.
No: The alarm is confirmed on the appliance and
remains active on the receiver until the error is
remedied.
-
Update (only visible if you have selected “Yes when
you confirmed):
Yes: Alarm repeats.
Temperature alarm depending on the set time
(see6.2.21 Temperature alarm )
(If you set the delay time of the alarm to “0”,
there will be no alarm repetition at the alarm
relay either.)
Door alarm after 1 or 4 minutes*
(see6.2.22Door alarm )
No: Alarm permanently confirmed.
Activating alarm forwarding
Fig. 163
Use
38 * Depending on model and options