Handleiding
Je bekijkt pagina 9 van 52

9IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Piping in refrigerating systems shall be so designed and installed to minimize the likelihood hydraulic
shock damaging the system.
• Provision shall be made for expansion and contraction of long runs of piping.
• Use a supply cord shall be between 1.5~3 m(4.9~9.8 ft) long and shall be either and extra hard usage or a
hard usage cord.
• Ampacities of supply cords and attachment plugs shall not be less than the current rating of the
appliance and shall be suitable for the application in accordance with national electrical installation
requirements.
• An unventilated area where the appliance using flammable refrigerants is installed shall be so
constructed that should any refrigerant leak, it will not stagnate so as to create a fire or explosion
hazard.
• Non-duct connected appliances containing A2L refrigerants with the supply and return air openings in
the conditioned space may have the body of the appliance may be installed in open areas such as false
ceilings not being used as return air plenums, as long as the conditioned air does not directly
communicate with the air of the false ceiling.
• For appliances with REFRIGERANT DETECTION SYSTEMS(Optional), the instructions shall include
the following:
For REFRIGERANT DETECTION SYSTEMS, the function and operation and required servicing measures.
For LIMITED LIFE REFRIGERANT SENSORS used in REFRIGERANT DETECTION SYSTEMS, the specified end
of life and instructions for replacement.
REFRIGERANT SENSORS for REFRIGERANT DETECTION SYSTEMS shall only be replaced with sensors
specified by the appliance manufacture.
LEAK DETECTION SYSTEM installed. Unit must be powered except for service.
This unit is equipped with a refrigerant leak detector for safety. To be effective, the unit must be
electrically powered at all times after installation, other than when servicing.
WARNING INSTRUCTIONS
WARNING
• To reduce the risk of explosion, fire, death, electric shock, injury or scalding to persons when using this
product, follow basic precautions, including the following:
Technical Safety
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
• Installation or repairs made by unauthorized persons can pose hazards to you and others.
• The information contained in the manual is intended for use by a qualified service technician who is
familiar with the safety procedures and equipped with the proper tools and test instruments.
• Failure to read and follow all instructions in this manual can result in equipment malfunction, property
damage, personal injury and/or death.
• When the power cord is to be replaced, the replacement work shall be performed by authorized
personnel using only genuine replacement parts.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified person in order to avoid a hazard.
• Installation MUST conform to the local building codes or, in the absence of local codes, the National
Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical Code Part1 CSA C.22. 1.