15. Testing instructions for the electric protective device
• Press the TEST button.
• The rocker turns to 0 position.
• Turn the rocker back to I position.
• If a fault occurs, contact an electrician.
16. Troubleshooting
Charging station is o, no lights on
Issue Corrective action
Mains voltage does not exist in supply con-
nectors (L1, L2, L3).
Make sure that the supply conductors are properly con-
nected. Make sure that there is power available.
The circuit breaker F0 is o. Turn the F0 on.
The PWR LED indicator on the controller is
not on.
Make sure that power supply to the controller is available.
Charging cable is locked in Mode 3 socket outlet
Issue Corrective action
Unexpected fault has occurred while pow-
er is on.
Turn o the power from the F0 and pull the charging
cable out from the socket.
Power is o. Switch Mode 3 lock into open position.
Conguration via web browser
Issue Corrective action
PC does not recognize micro USB plug and
connection to the controller cannot be es-
tablished via web browser.
Make sure from Windows operating system settings via
“Device Manager” that RNDIS network adapter is avail-
able. If not, contact your local IT support.