SECTION II ASSEMBLY AND INSTALLATION
The KwiKool Iceberg KIBXX II systems provide portable cooling to match customer needs. These
systems come with touchscreen controls, internal condensate pumps, freeze protection, integral
condensers, and other features. Models exist in the 1.1-ton, 1.5-ton, 2-ton, 2.5-ton, 3.5-ton, 5-ton and
10-ton ranges.
A PREVIEW THE INSTALLATION SITE
Before moving the KIB/KWIB into place, verify the following:
The direction to which the supply air is going
The direction from which the return air is coming (cooling)
The direction to which the hot air exhaust is going (heat removal)
The direction from which the condenser make-up air is coming
The location of the power supply
The direction to which the condensate water will be pumped, or where the condensate bottle is
placed
Position the unit based on these guidelines for best results.
NOTE
Leave at least five feet of open space around the return air inlet
for the filter to ensure proper operation.
B AIR CHUTES (AS AN OPTIONAL ACCESSORY).
Install supply air flanges to the front of the KwiKool unit above the control panel. (See instructions in the
air chute kit for specific procedures). Install air chutes on the flanges with included clamps.
C CONNECT CONDENSATE TANK OR DRAIN LINE
The 5-gallon condensate tank is equipped with a float switch that shuts the unit’s compressor off, alerts
operators with an alarm, and displays CF (“Condensate Full”) when the condensate tank is full. (Turn
the system to OFF to stop the alarm). This prevents accidental water overflow on the floor. Operators
can connect ¼” ID tubing (sold separately) to the ¼” OD barbed fitting located in the power cord pocket
on the back of the KIBXX II and pump condensate water to the external condensate tank that comes
standard with the system or up to 20 feet straight up and out over 100 feet to an approved drain source.
All KIBXX-II systems have a condensate pump built in.
CAUTION
The alarm will clear automatically upon emptying the 5-gallon tank
and reconnecting it. If connecting to a permanent drain, do NOT
connect or use the equipped 5-gallon tank. Use the by-pass jack
installed from the factory.