NOTE
Standard water-cooled KWIBXX II Iceberg Series models are not
designed to operate with water temperatures below 40 degrees F.
Low-ambient temperature controls must be special ordered at an
additional cost.
CAUTION
Temperatures below 40 degrees F will cause evaporator coil
freezing and possible compressor damage. This can void the
warranty.
C CAPACITY & TEMPERATURE SETTINGS
Sizing of the Iceberg Series is based on matching capacity to a specific heat load while maintaining a
72-degree F temperature. To reach temperatures below 72 degrees F, the Iceberg Series System must
have extra capacity.
CAUTION
We recommend that the operator not set the temperature set point
below 72 degrees F, unless there is excess cooling capacity
beyond the heat load, since this may cause the unit’s evaporator
coil to freeze up.
D POSITIONING OF ICEBERG SERIES SYSTEMS
Do not place the Iceberg Series System in direct sunlight. The system should be positioned so that the
output of the Iceberg Series System can be focused as close to the heat generating equipment as
possible with the front grill fully exposed.
CAUTION
Do not block the front of the Iceberg Series System, since this will
cause a restriction in the airflow and can cause low performance
and/or evaporator coil freezing.