15
G CONDENSATE PUMP & HIGH LEVEL ALARM
All KWIBXX II & KIBXX II Iceberg models are factory equipped with an internal high lift condensate
pump. Iceberg Series condensate pumps are able to pump the condensation either to the factory
supplied condensate bottle, or to a drain or other location as required by the application. The internal
pump is rated at 20 feet of head pressure. This means it can pump water to a maximum of 20 feet
vertically. Each pump is equipped with an overflow safety cut-off switch that automatically shuts the
Iceberg unit down, sounds an audible alarm and displays a fault code (CP). This prevents accidental
flooding of the conditioned space. Automatic reset upon fault correction, see the troubleshooting guide
H CONDENSATE TANK & HIGH LEVEL ALARM
All KIBXX II Iceberg models come standard with an external condensate tank. The tank is equipped
with an overflow safety cut-off switch. When the tank is full, the safety will automatically shut down the
Iceberg Series System, sound an audible alarm and display a fault code (CF). This prevents accidental
flooding of the conditioned space. If using the supplied bypass plug and not using the tank, this alarm is
nonfunctional.
I POWER/PHASE MONITOR (OPTIONAL)
The Iceberg Series Phase Monitor is available as an option on all 3-phase Iceberg Series models. The
phase monitor samples the power supply for low or high voltage, out of phase and loss of phase. If any
of these power conditions arise, the Phase Monitor will automatically shut down the Iceberg Series
system, sound an audible alarm and display a fault code (PH). This alarm will reset automatically when
the power is restored to normal.
J SERVICE PORTS
Service Ports are located in the filter access compartment in the front of the Iceberg Series system
below the control panel. This gives service personnel a connection point for service gauges to monitor
the operating pressures of the mechanical system.
K SIGHT GLASS/MOISTURE INDICATOR
The Sight Glass is located in the Discharge air make-up inlet on KIBXX II systems and located on the
rear panel above the condenser water connections on KWIBXX II systems. Remove the rubber
grommet to view through the sight glass. This feature allows operators and service personnel to view
the condition of the refrigerant returning to the evaporator coil. Used as a diagnostic tool by qualified
personnel.