KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS KWIKOOL
23
FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
The numeral 99
flashes on display.
Ambient room temperature
over 99 degrees F.
Iceberg Series System is working properly.
Cooling will continue but display cannot show
more than two digits regardless of temperature.
Lowering of room temperature to 99 or less will
end the flashing.
The numeral 60
flashes on display.
Ambient room temperature
under 60 degrees F.
Iceberg Series Cooler is working properly. Limits of
Iceberg Series Cooler have been reached and
further cooling is not possible. Operating
temperatures are 65 - 105 degrees F.
APPENDIX
A SYSTEMS EQUIPPED WITH A PHASE MONITOR
FAULT
POSSIBLE CAUSE
POSSIBLE SOLUTION
Iceberg Series System displays
PH, audible alarm sounding
during start up, phase monitor
displays, REV PHASE
Phase monitor detects reverse
phasing, lost phase or improper
power incoming.
Exchange any line voltage wire
with the other. Do not change
the Green wire. Auto reset upon
correction.
Iceberg Series System displays
PH, audible alarm is sounding
during start up, and phase
monitor displays current
incoming power is low
Phase monitor detects voltage
lower than factory setting.
Verify incoming power.
Raise incoming voltage.
Adjust incoming power
tolerance on monitor if
authorized.
Auto reset upon correction.
Iceberg Series System displays
PH, audible alarm is sounding,
and phase monitor displays
current incoming power is high
Phase monitor detects voltage
higher than factory setting.
Verify incoming power.
Lower incoming voltage.
Adjust incoming power
tolerance on the monitor if
authorized.
Auto reset upon correction.
System starts up but goes into
visual and audible alarm.
Displays PH when the
compressor starts
Phase monitor detects voltage
drop.
Observe the phase monitor
on start for fault lights and
adjust the monitor
accordingly.
Verify incoming power.
Auto reset upon correction.
Check wire size and voltage
drop.
Iceberg Series System displays
PH, Alarm is sounding during
start up or during operation, and
phase monitor displays “Back
Fault”
A fault has been detected from
one of the Iceberg Series
System’s condenser motors.
Inspect motor components for
faulty or loose connections and
proper operation. Call 1-800-
594-5665 (1-800-KWIKOOL) for
guidance.