KWIKOOL   KIBXX II/KWIBXX II ICEBERG SERIES SYSTEMS   
20 
FAULT 
POSSIBLE CAUSE 
POSSIBLE SOLUTION 
Iceberg Series 
System Displays 
HP. Audible alarm is 
sounding during 
start up or while 
operating. 
Microprocessor board has 
detected high pressure. 
The High Pressure switch 
is tripped. 
High-pressure trip is normally caused by reduced 
or stopped Condenser Air flow on KIBXX II, or 
water flow on KWIBXX II.  
  Check for restriction in ducting on air-cooled 
systems or restrictions in water line sets on 
water-cooled systems. 
  Check for Condenser Air system ventilation 
(See Section II. C. 4) or source water input on 
KWIBXX II. 
  For KIBXX II, check condenser motors and/or 
blowers for proper operation. 
  On KIB12023 II or KIB12043 II check VFD 
(motor drive) for trip. Reset if necessary. 
  High-pressure reset switch is a manual reset 
type. To reset, open filter door. The button is 
located above the filter. Press button to reset 
(the operator should feel a click). 
Iceberg Series 
System Displays LP 
(Low Pressure 
(Freon)), Audible 
alarm is sounding 
during start up or 
while operating. 
Microprocessor board has 
detected low pressure. This 
alarm may cycle on and off. 
  Check air filter and replace if dirty. 
  Make sure nothing is blocking the filter inlet. 
  Check for icing on coil. 
  Resets automatically when fault condition is 
corrected. 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance if condition continues. 
Iceberg Series 
System Displays 
PH, Audible alarm is 
sounding during 
start up. 
Phase Monitor (if equipped) 
has detected incoming 
power issue on equipped 
systems. 
See Troubleshooting Guide for systems equipped 
with a phase monitor (Appendix - Part B). 
Audible alarm fails to 
clear on start up or 
while operating. 
Iceberg Series 
System displays FS. 
Microprocessor has 
detected freezing on the 
evaporator coil if the 
system has a factory 
installed freeze sensor. 
(Special order). 
Check for freezing on the evaporator coil and turn 
the system off to let it thaw out. Call 1-800-
KWIKOOL if the system is not equipped with a 
freeze sensor. Auto resets upon correction. 
Audible alarm fails to 
clear on start up or 
while operating. 
Iceberg Series 
System displays A1. 
Microprocessor has 
detected customer installed 
normally closed circuit 
open. 
Review aftermarket device installed for fault that is 
opening the circuit. Auto resets upon correction 
Audible alarm fails to 
clear on start up or 
while operating. 
Iceberg Series 
System displays A2. 
Microprocessor has 
detected customer-installed 
normally-open circuit 
closed 
Review aftermarket device installed for fault that is 
closing the circuit. Auto reset upon correction. 
Call 1-800-594-5665 (1-800-KWIKOOL) for 
guidance. 