Installation
Central grid and system protection is required in some
countries. This monitors the voltage and frequency in the
grid and in the event of a fault, shuts down the photo-
voltaic systems by means of a circuit breaker.
If your energy supplier requires central grid and system
protection for your system, install an external monitoring
device, which switches o the inverter via a normally
open or normally closed contact. An additional circuit
breaker is not necessary, as this is not required by the
inverter's internal switches.
1. De-energise the mains cable.
2. Mount the monitoring device in the control cabinet or
power distributor.
3. Correctly route the communication cable from the
inverter to the control cabinet and connect according
to the wiring diagram provided by manufacturer.
4. Pass the communication cable through the cover for
the COM2 connection panel. Seal connection with
sealing ring and union nut.
5. Connect the communication cable to the plug con-
nector for the communication interface. Please note
the pin assignment.
Torque: 0.2 Nm.
DANGER
RISK OF DEATH DUE TO ELECTRI-
CAL SHOCK AND DISCHARGE!
De-energise all devices and secure
them against being switched on
again.
INFO
Requirements of communication
cable:
n Wire cross section:
0.34 - 1.5 mm
2
(rigid)
0.34 - 1.0 mm
2
(flexible)
n Length max. 30
n Length of stripped insulation ap-
prox. 5 mm
3
2
3
4
5
6
7
8
9
10
1