Important Considerations
The air conditioner must be installed by a licensed trade professional.
When filling the combustible refrigerant, incorrect operation may cause serious injury or
damage to the appliance.
A leak test must be done after installation is completed.
A safety inspection must be conducted before performing maintenance or repairs on an
air conditioner using combustible refrigerant to ensure that the fire risk is reduced to
minimum.
It is necessary to operate the machine according to established safety protocols to
ensure that any risk arising from combustible gas or vapor during operation is
minimised.
Requirements for the total weight of filled refrigerant and the area of a room to be
equipped with an air conditioner are shown in the following Tables GG.1 and GG.2.
Maximum Charge and the Required Minimum Floor Area
m
1
= (4 m
3
) x LFL, m
2
= (26 m
3
)) x LFL, m
3
= (130 m
3
) x LFL.
Where LFL is the lower flammable limit in kg/ m
3
, R32 LFL is 0.306 kg/ m
3
.
For the appliances with a charge amount m
1
< M = m
2
:
The maximum charge in a room must be in accordance with the following: m
max
= 2.5 x
(LFL)
(5/4)
x h
0
x (A)
1/2
.
The required minimum floor area Amin to install an appliance with refrigerant charge M
(kg) shall be in accordance with following: A
min
= (M/ (2.5 x (LFL)
(5/4)
x h
0
))
2
.
Table GG.1 - Maximum Charge (kg)
Category
LFL
(kg/m)
3
h
0
(m)
Floor area (m
2
)
4 7 10 15 20 30 50
R32 0.306
1 1.14 1.51 1.8 2.2 2.54 3.12 4.02
1.8 2.05 2.71 3.24 3.97 4.58 5.61 7.254
2.2 2.5 3.31 3.96 4.85 5.6 6.68 8.85