Janitza 800-CT24 handleiding
Handleiding
Je bekijkt pagina 53 van 60

www.janitza.com
53
800-CT24 module
13. Technical specifications
General
Net weight 120g (0.26lb)
Device dimensions
W=248mm (w=9.76in), H=42mm (h=1.65in),
D=37mm (d=1.46in)
Mounting orientation As desired
Fastening/mounting - Suitable DIN rails
(35mm/1.38in)
TS 35/7.5 according to EN60715
TS 35/10
TS 35/15 x 1.5
Protection against foreign matter and water IP20 according to EN60529
Impact resistance IK07 according to IEC 62262
Environmental conditions during operation
The module
· Must only be operated with suitable basic devices (see Sect. “Tab. Suitable basic devices” on p. 2).
· Is for weather-protected and stationary use.
· Fulfills operating conditions according to DIN IEC 60721-3-3.
· Has protection class II according to IEC 60536 (VDE 0106, part 1), a ground wire connection is not required!
Working temperature -10°C(14°F) .. +55°C(131°F)
Relative humidity 5 to 95% at 25°C (77°F), no condensation
Pollution degree 2
Ventilation No forced ventilation required.
Transport and storage
The following specifications apply for devices transported and stored in the original packaging.
Free fall 1m (39.37in)
Temperature K55: -25 °C (-13 °F) to +70 °C (158 °F)
Relative humidity 0 to 95% at 25°C (77°F), no condensation
Current measurement
Rated voltage for the LP current transformers 333mV
Channels 24
Measuring range 0 ... 400mV
Crest factor 1.8
Overload for 1s 1V
Resolution 16 bit
Sampling frequency 6.8kHz
Frequency of the fundamental oscillation 40Hz .. 70Hz
Harmonics 1 .. 15 (odd only)
13.1 Technical data
Bekijk gratis de handleiding van Janitza 800-CT24, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Janitza |
| Model | 800-CT24 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 9037 MB |