7.6 Flue and air supply duct
7.6.1 Flue, materials and compounds
For the installation of the flue and
air supply duct material, see the
manual included with the materials.
Further technical information and
specific assembly instructions are
available upon request.
Only plastic PP flue material is allowed.
Make sure that the socket connections
of the flue and air supply duct materials
are correctly sealed. Incorrect connection
of the flue and the air supply duct
can lead to hazardous situations or
result in personal injury. Check all flue
components for tightness.
Do not use screws or nails to mount the
flue system as leakage can occur only
use the correct support brackets at the
recommended distances.
Do not use any sort of grease when
connecting the flue system. Use water
instead. The sealing rubbers can be
adversely aected when grease is applied
and can also become disconnected.
Do not mix any components, materials
or ways of connecting from dierent
manufacturers as they must be approved
by Intergas Heating Ltd.
Flue materials
Execution Diameter Material Remark
Rigid Concentric Ø100/60 mm Plastic T120 Plastic; Approved material with lip ring sealing.
Rigid single wall Ø80 mm Plastic T120 Plastic; Approved material with lip ring sealing.
Flexible Concentric Ø100/60 mm Plastic T120
Air supply materials
Execution Diameter Material Remark
Rigid single wall Ø80 mm Plastic T120 Plastic; Approved material with lip ring sealing.
Flexible Ø100/60 mm Plastic T120 Plastic; Approved material with lip ring sealing.