7.5.1 Connecting Modulating OpenTherm thermostat
7.5.2 Connecting on/o volt free TPI room thermostat
7.5.3 Connecting 230V room thermostat
7.5 Connecting room thermostat
The boiler is supplied with an OpenTherm connection X13 1/2 .
This allows the connection of the Intergas Comfort Touch as
well as other modulating OpenTherm thermostats without
any additional modifications. The Xclusive is also suitable for
OpenTherm Smart Power.
Position the thermostat in a room that functions as a
reference point (in general, the living room or hall).
Remove the link and connect the modulating thermostat to
terminals 1/2 X13 (also see §12.1); the polarity of the wires
is not important in this situation.
If you would like to make use of the *domestic hot water on/
o switch function of the OpenTherm thermostat, the DHW
comfort function must be set to ‘eco’ or ‘on’ (see §9.1.2) and
parameter P074 must be set to 0.
*Dependant on model type and availability for further
information, consult the manufacturers instructions for the OT
room thermostat installed.
The boiler is suitable for connection to the following room
thermostats:
OpenTherm (OT) thermostat/Intergas Comfort Touch
On/o thermostat (TPI)
RF thermostat; see §9.1.4.
The boiler is suitable for connection to a 2-wire on/o room
thermostat.
Position the thermostat in the room that functions as a
reference point (in general, the living room or hall).
Remove the link and connect the TPI room thermostat to
Connector 1/2 X13 (also see §12.1); the polarity of the wires
is not important in this situation.
This should be wired to connector X3 1/2.
Position the thermostat in the room that functions as a
reference point (in general, the living room or hall).
Connect the 2-wire room thermostat to terminals 1/2
X3 (also see §12.1); the polarity is not important in this
situation however terminal 1 (L) is the supply from the PCB
90 to 230v ac, terminal 2 (S) is the demand signal from the
room thermostat to the boiler.
Connecting 230V room thermostat
X4 X3 (230V)
12
On
O
12
LS
If both OpenTherm and on/o TPI
thermostats are connected, the on/o
TPI thermostat will have priority over the
OpenTherm thermostat.
IMPORTANT (HIGH VOLTAGE)
Isolate the appliance from the electrical
supply before connecting the thermostat.
X13
12
On
O
2 1
Remove the yellow link
wire prior to connecting
the room thermostat
Connecting Intergas Comfort Touch,
OpenTherm and/or on/o volt free TPI
room thermostat