Fault code Description Possible cause / solution
F007F007
No or insuicient
ionisation current.
► Check ionisation/ignition pin is clean and correctly located.
► Check ionisation/ignition pin wiring is connected not damaged.
► Replace ionisation/ignition pin.
F008F008
Incorrect fan speed
detected
► Check fan wiring.
► Check and/or replace fan assembly .
► Replace PCB.
F009F009
Internal PCB fault. ► Replace PCB.
F010, F011F010, F011
Heat exchanger Sensor
S0 fault.
► Check wiring to heat exchanger sensor S0 (ensure its connected
and not damaged).
► Check heat exchanger sensor S0 resistance values are correct.
► Check for the correct location of heat exchanger sensor S0.
► Replace heat exchanger sensor S0.
F012F012
Flue gas sensor fault S5.
► Check wiring to flue gas sensor S5 (ensure its connected).
► Check flue gas sensor S5 resistance values are correct .
► Check for the correct location of flue gas sensor S5.
► Replace flue gas sensor S5.
f014f014
Heat exchanger sensor
S0 mounting fault.
► Heat exchanger sensor S0 is not mounted correctly. Attach the
sensor correctly.
f015f015
Heating sensor S1
mounting fault.
► Central heating flow sensor is not mounted correctly. Attach the
sensor correctly.
f016f016
DHW sensor S3
mounting fault.
► Domestic hot water sensor S3 is not mounted correctly. Attach
the sensor correctly.
F018F018
Flue and/or air supply
duct is blocked/restricted.
► Check the flue and the air supply duct including seals or gaskets.
► Clean the flue and/or the air supply duct.
F019F019
Boiler memory module
fault.
► Check BMM wiring or connector for damage.
► Replace BMM.
F027F027
Short circuit of outdoor
weather compensation
sensor S6.
► Check wiring to outdoor sensor and ensure its connected
correctly and not damaged.
► Check the outdoor sensor resistance values are correct.
► Replace the outdoor sensor.
f028f028
Reset error.
► Check the reset button for unintentional operation (e.g. cleaning
of control panel).
► Replace the PCB.
f029f029
Gas valve fault.
► Check the gas valve wiring, coil resistances.
► Replace the PCB.
F031F031
CH flowsensor fault S1.
► Check wiring of central heating flow sensor for damage and
ensure its connected correctly.
► Ensure the central heating flow sensor resistance values are
correct.
► Check for the correct operation of central heating flow sensor S1.
► Replace central heating flow sensor S1.
IMPORTANT
► Any replacement components must be
original Intergas parts.
► Using 3rd party components or installing
them incorrectly can lead to serious
consequences, with a risk to health,
occupants or buildings.
Bekijk gratis de handleiding van Intergas Xclusive 24, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Intergas |
| Model | Xclusive 24 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 12726 MB |