Intergas Heating Ltd 59
10.2.7 No hot water (DHW)
Possible causes:
Solution:
Flow sensor not functioning.
DHW flow < 1.5 l/min.
Replace the flow sensor.
No
No voltage at the flow sensor (5V DC).
Check the wiring according to the diagram.
No
Burner not firing on DHW: S3 faulty.
Replace S3.
No
Burner does not ignite.
See burner does not ignite.
10.2.8 Hot water does not reach temperature
Possible causes:
Solution:
DHW flow to high.
Adjust the inlet assembly.
No
Temperature setting for water circuit too
low.
Set the hot water circuit, depending on the desired temperature.
No
No heat transfer as a result of lime scale or
fouling in the heat exchanger DHW side.
Descale or flush the exchanger DHW side.
No
Cold water temperature <10°C.
10.2.9 LED on CH pump is flashing alternately red and
green.
Possible causes:
Solution:
Mains voltage to high or to low.
Check the mains.
No
Temperature of the pump is to high
Check the water and environment temperature.
10.2.10 LED on CH pump is flashing red.
Possible causes:
Solution:
Pump is not running
Reset the pump by shutting of the boiler (stand-by or powerless) for at least
20 seconds.
Note: If the pump is set on “continuously active” (parameter 2 = 1) the boiler
must be made powerless for at least 20 seconds.